The INCINOMITE Model J121-DS gas burner features direct main
flame spark ignition and solid state electronic flame verification.
In the United States, installation must conform with local
codes or, in the absence of local codes, National Fuel
Gas Code, ANSI Z223.1-latest edition(s) available from
American National Standard Institute. Further reference
should be made to the recommendation of your fuel
supplier.
Note: Any additions, changes or conversions required in
order for the gas utilization equipment to satisfactorily
meet the application needs must be made by a MIDCO
distributor (or other qualified agency) using factory
specified and approved parts.
In Canada, installation must conform with local codes or,
in the absence of local codes, with Installation Codes
for Gas Burning Appliances and Equipment, CGA
Standard CAN/CGA 1-B149.1 or 2.
INSTALLER: Inform and demonstrate to the user the
correct operation and maintenance of this gas
utilization equipment. Inform the user of the hazards
of storing flammable liquids and vapors in the vicinity
of this gas utilization equipment and remove such
hazards. CODE COMPLIANCE IS THE SOLE
RESPONSIBILITY OF THE INSTALLER.
WARNING: If the information in
these instructions is not followed
exactly, a fire or explosion may result,
causing property damage, personal
injury or death.
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appli
-
ance.
Installation and service must be per
-
formed by a qualified installer, service
agency or the gas supplier.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical
switch; do not use any phone in
your building.
Immediately call your gas
supplier from a neighbor's
phone. Follow the gas suppliers'
instructions.
If you cannot reach your gas
supplier, call the fire department.
USER: Retain this manual for future reference.
If other than routine service or maintenance as
described in this manual is required, contact a
qualified service agency. DO NOT ATTEMPT
REPAIRS. An inadvertent service error could
result in a dangerous condition.
: The following terms are used to identify hazards, safety precautions or special
notations and have standard meanings throughout this manual. When you see the safety alert symbol and one of the
safety information terms as shown below, be aware of the hazard potential.
DANGER: Identifies the most serious hazards which will result in severe personal injury or death.
WARNING: Signifies a hazard that could result in personal injury or death.
CAUTION:
Identifies unsafe practices which would result in minor personal injury or product and property damage.
Installation and Service Instructions
Midco International Inc.
4140 West Victoria Street Chicago, Illinois 60646
tel 773.604.8700 fax 773.604.4070
web www.midco-intl.com e-mail [email protected]
602
8471 15
Printed in USA
Incinomite
Model J121-DS
Gas Burner
Quality Designed for Proven Performance
Page view 0
1 2 3 4 5 6 ... 11 12

Summary of Contents

Page 1 - Incinomite

The INCINOMITE Model J121-DS gas burner features direct mainflame spark ignition and solid state electronic flame verification. In the United Stat

Page 2 - Part 1 Installation

Cleaning of the blower wheel is usually the only service required. Need forcleaning is required if the inlet screen or blower wheel shows an accumulat

Page 3

If the Electronic control is changed, the replacement must be identical as to themake and model number, or must be an authorized substitute.WARNING: E

Page 4

12Trouble ChartC. Check for 24V* between strip terminals 6 to 10. No voltage, transformer is defective.D. Check for 24V* between strip terminals 5 an

Page 5

Part 1 InstallationSpecifications1Part 1 Installation BURNER AIR DELIVERYApproximate Air Delivery at Zero Draft…...180 SCFM2MINIMUM GAS PRESSURE LIS

Page 6

3Install the INCINOMITE burner(s) in location(s) specified by the incineratormanufacturer. It should be positioned approximately level with the top of

Page 7

chamber over-fire draft, 0 to minus 0.5" W.C., a fixed damper should be installed inthe vent connector between the barometric and chimney to rest

Page 8 - Part 2 Service

5Part 1 Installation______________________________________________________Installation wiring to the burner must conform to local codes, or, in their

Page 9

from reaching an explosive level, periodically purge the incineration chamber as described in Step 5.9. Observe the ignitor flame. If it is weak,

Page 10 - Trouble Chart

7Figure 3 Control ComponentsPart 1 InstallationFigure 2 Wiring Diagram

Page 11 - TROUBLE CHART

12. The actual NATURAL gas firing rate in BTU per hour can be determined by timing the gas meter. Accurately time the meter test dial for one revolut

Page 12

SPARK TEST—Main Manual Shut-Off Valve must be off. Place the IgnitorAssembly on top of the burner with the electrode ends visible and good metal tomet